| DOOR & FRAME | |
|---|---|
| Material | 8040 T-5 Temper Aluminum |
| Tensile Strength | 30,000 psi |
| Panel Options | Test | Result |
|---|---|---|
| 8 mm Twin-Wall Polycarbonate / Self-ignition temperature: 450 deg C |
ASTM E-84 | Class A |
| ASTM D635 | CC1 |
The hot aisle containment system uses a cabinet-independent frame with a translucent exhaust duct, edge seals, automatic sliding double doors, adjustable filler panels or brushes, and full-height blanking panels to fully seal the aisle, manage airflow in a closed return system, and accommodate varying cabinet heights, widths, and layouts.
| DOOR & FRAME | |
|---|---|
| Material | 8040 T-5 Temper Aluminum |
| Tensile Strength | 30,000 psi |
| Panel Options | Test | Result |
|---|---|---|
| 8 mm Twin-Wall Polycarbonate / Self-ignition temperature: 450 deg C |
ASTM E-84 | Class A |
| ASTM D635 | CC1 |
① Hot Aisle Containment – Cabinet-independent frame and translucent exhaust duct cover the contained aisle to capture and vent airflow out of the aisle. Used as part of a closed return for the air handling system.
② Edge Seal – Flexible, curved seal used around the top of the duct to complete seal with overhead drop ceiling tiles.
③ Aisle Containment Double Door Assembly – Sliding double doors with automatic closing features and large transparent panels. Attaches to the ends of the Frame Supported Exhaust Duct to seal the ends of the contained aisle (this system not compatible with Single Door Assembly).
④ Adjustable Height Filler Panel/Brush – Adjustable height panels/universal cabinet end panel or brush used above standard equipment cabinets to seal gaps between the 52U Frame Supported Exhaust Duct and the cabinets. Alternately, Universal Cabinet End Panels adjusts in both height and width.
⑤ Full Height Blanking Panel – Translucent panel and seal used to fill gaps where entire cabinets are omitted from the cabinet row. Easy to trim to match required width. Supports “roll-in/roll-out” deployment and variable length cabinet rows created when cabinets of differing widths are deployed in the same row.
SOLUTION OVERVIEW